🔍 Büyüt
| Teknik Parametre | Değer |
|---|---|
| Modelcode01 | IC7-60FA3N05-658AE20F3 |
| Modelcode02 | +AGCX |
| Modelcode03 | +BAPX+BDBA |
| Modelcode05 | +DAAU |
| Modelcode04 | +BEF1+BF20+CAR0 |
| Typecode Part 1 | 7FC-AUFA3N05-658AE20F3 |
| Typecode Part 2 | -000216987 |
| ECCN EU | Y901||Y901 |
| ECCN US | 3A999.a||3A999.a |
| Recommended Plant | ERR01||ERR01 |
| Calculated Net Weight [kg] | 179.630 |
| Calculated Gross Weight [kg] | 216.740 |
| Vendor | ERR01||Cannot Determine Vendor |
| Efficiency class-Relative loss | IE2 - 1.78%||IE2 - 1.78% |
| Main unit Depth | 482 mm / 19 in||482 mm / 19 in |
| Enclosure rating | IP20 / OPEN TYPE||IP20 / OPEN TYPE |
| Main unit Height | 1578 mm / 62.1 in||1578 mm / 62.1 in |
| Input frequency | 50/60Hz||50/60Hz |
| Main unit Width | 508 mm / 20 in||508 mm / 20 in |
| Short circuit current rating | 100kA||100kA |
| Input Voltage | 3x380-500V||3x380-500V |
| Additional drive features 2 | +DE2X||None |
| Additional drive features 4 | +DG4X||None |
| Additional drive features 5 | +DH5X||None |
| Additional drive features 3 | +DF3X||None |
| Cable entry and EMC plate | +AAST||Standard plate |
| Customer specific application | +DBXX||None |
| Communication interface, X0 | +BBEL||Ethernet port, no protocol##Control card with Ethernet port X0, but no embedded protocol - can beupgraded later |
| Control panel | +BF20||Control Panel 2.8 OPX20##Control Panel with user interface, status and fieldbus indicators |
| Customer-specific label | +EJXX||None##No customer specific information printed on product label |
| DC terminals | +ALXX||None##No DC terminals |
| Customization file package ID | +EAXXXXXX||No customization##No customer specific settings |
| Communication interface, X1/X2 | +BAPX||PROFINET RT OS7PR + Multilic##PROFINET RT - Application class 3. MRP, shared device, PROFIenergy, PROFINET diagnostics (ALARM CR) and extended diagnostics. To enable PROFISAFE use the configuration group "Functional Safety". With fieldbus multi license. |
| High speed enabled | +DI6X||No##Output frequency limited to 590 Hz |
| Extra environmental protection | +AGCX||Coated boards##Coated printed circuit board for extra protection |
| EMC category | F3||C3 category##Suitable for installation in the 2nd environment only, max. motor cable length up to 300 meters |
| Heat sink access panel | +APXX||None##No heat sink access plate |
| Humidity protection device | +AHXX||None##None |
| Interface board | +BISR||MicroSD card reader and RTC##Interface board, MicroSD card reader and Real Time Clock (RTC) withbattery backup |
| Integrated brake chopper | +ACXX||None##No brake chopper |
| Integrated common-mode filter | +AIXX||None##No High Frequency common mode filter integrated |
| Current rating | -658A||658 A |
| Mains input device | +AJXX||None##No mains device |
| Functional safety | +BEF1||STO, not upgradable##STO (Safe Torque Off) only - not possible to upgrade later with FSrelated functionality |
| Language package | +EL01||Global##Global language package - See Technical Documentation for detailedinformation |
| Frame designation | FA11||FA11 |
| Mains voltage | 05||380-500 V AC##Voltage range 380-500 V AC - Current rating given at 400V AC |
| Option slot A | +CAR0||Relay Option OC7R0##Option with 3 Relays (2xNO/NC & 1xNO, 24 V DC/2 A or 250 VAC/3 A) |
| Option slot B | +CBXX||None, not upgradable##Option slot is not available |
| Product group | IC7-60||iC7-60##Product is based on iC7-60 hardware series |
| Product category | FA||Frequency converter,air-cooled |
| Option slot C | +CCX0||None##No option in option slot. Field upgrade possible |
| Option Slot E | +CEX0||None##No option in option slot. Field upgrade possible |
| Option slot D | +CDX0||None##No option in option slot. Field upgrade possible |
| Product software ID | +ECXXX||Latest released version##Latest official released version |
| Product series | +DAAU||iC7-Automation |
| Standard I/O | +BDBA||4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO##Basic I/O (4 DI, 2 DI/DO, 2 AI, 1 AO, 2 NO/NC relays) |
| Protection rating | E20||IP20/Open Type##IP20/UL Open Type frames are designed for installation in enclosedcabinets and similar set-ups. |
| Touch protection | +AMXX||None##No touch protection |
| Product specific marine cert. | +VBXX||None##No approval |
| Technical documentation | +EGIN||Installation guide##Includes Installation Guide and Safety Guide |
| Power rating | 355||355 kW/500 hp |
| Output frequency | 0-590Hz||0-590Hz |
| Continous current IH (1/10min) | 588/520A||588/520A |
| Continous current IH (1/5min) | 480/456A||480/456A |
| Continous current IL (1/10min) | 658/590A||658/590A |
| Overload current IH (1/10min) | 882/780A||882/780A |
| Input current in High Overload | 566/501A||566/501A |
| Overload current IH (1/5min) | 720/684A||720/684A |
| Overload current IL (1/10min) | 724/649A||724/649A |
| Input current in Normal Overlo | 633/568A||633/568A |
| Maximum Power Loss LO [W] | 7576||7576 |
| Typical motor power PH2 (150%) | 250kW(400V)/350HP(460V)||250kW(400V)/350HP(460V) |
| Typical motor power PL (110%) | 355kW(400V)/500HP(460V)||355kW(400V)/500HP(460V) |
| Typical motor power PH (150%) | 315KW(400V)/450HP(460V)||315KW(400V)/450HP(460V) |
| Ambient temp. normal overload | 40°C/104°F||40°C/104°F |
| Ambient temp. high overload | 45°C/113°F||45°C/113°F |
| Product Catalog | NO_VIEW||NO VIEW |
| Product View (Switch) | GLBL||Global (Standard) |
| Additional drive features 1 | +DD1X||None |
| Product type | 3N||3~##Three phase supply - rectifier input |
| Control Board type | A5E||Advanced Ethernet A5E##Advanced control board with Dual Ethernet interface and 24V external supply |
| Input curent HO2 (1/5 min) | 462/439A||462/439A |
| Ambient temp HO (1/10 min) | 45°C/113°F||45°C/113°F |
| Ambient temp HO2 (1/5 min) | 45°C/113°F||45°C/113°F |
| Input current HO (1/10 min) | 566/501A||566/501A |
| Ambient temp LO (1/10 min) | 40°C/104°F||40°C/104°F |
| Input current LO (1/10 min) | 633/568A||633/568A |
Evet, DES Teknoloji, Danfoss Türkiye partneridir. İncelediğiniz Danfoss iC7-Automation Frequency converter,air-cooled, 3~, 380-500 V AC, 658 A, 355 kW/500 hp, IP20/Open Type, FA11 ürünü %100 orijinal olup fabrika garantisi altındadır.
Evet. DES Teknoloji olarak uzman mühendis kadromuzla Danfoss sürücüleriniz için yetkili bakım, onarım, yedek parça ve test hizmeti sunmaktayız.
Satış sonrası mühendislik hizmetlerimiz kapsamında cihazın pano montajı, parametre ayarları ve sahada devreye alınması konularında teknik destek sağlamaktayız.
Sayfadaki 'Proje İçin Teklif Alın' butonuna tıklayarak veya iletişim numaralarımızdan satış mühendislerimize ulaşarak özel iskontolu fiyat teklifinizi hemen alabilirsiniz.