🔍 Büyüt
| Teknik Parametre | Değer |
|---|---|
| Input frequency | 50/60Hz||50/60Hz |
| Product Catalog | NO_VIEW||NO VIEW |
| Modelcode05 | +DAAU |
| Enclosure rating | IP54 / TYPE 12||IP54 / TYPE 12 |
| Modelcode01 | IC7-60FA3N05-1120E54F3 |
| Modelcode02 | +AGCX+AJFD |
| Main unit Height | 2044 mm / 80.5 in||2044 mm / 80.5 in |
| Overload current IH (1/10min) | 1500/1344A||1500/1344A |
| Input current in High Overload | 963/863A||963/863A |
| Overload current IH (1/5min) | 1340/1176A||1340/1176A |
| Overload current IL (1/10min) | 1232/1131A||1232/1131A |
| Continous current IH (1/10min) | 1000/896A||1000/896A |
| Continous current IH (1/5min) | 880/784A||880/784A |
| Efficiency class-Relative loss | IE2 - 1.82%||IE2 - 1.82% |
| Continous current IL (1/10min) | 1120/1028A||1120/1028A |
| Main unit Depth | 510 mm / 20.1 in||510 mm / 20.1 in |
| Touch protection | +AMXX||None##No touch protection |
| Product specific marine cert. | +VBXX||None##No approval |
| Modelcode04 | +BEF2+BF20 |
| ECCN US | 3A999.a||3A999.a |
| Technical documentation | +EGIN||Installation guide##Includes Installation Guide and Safety Guide |
| Power rating | 630||630 kW/900 hp |
| Option slot D | +CDX0||None##No option in option slot. Field upgrade possible |
| Product software ID | +ECXXX||Latest released version##Latest official released version |
| Product series | +DAAU||iC7-Automation |
| Modelcode03 | +BAPR+BDBA |
| Standard I/O | +BDBA||4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO##Basic I/O (4 DI, 2 DI/DO, 2 AI, 1 AO, 2 NO/NC relays) |
| Protection rating | E54||IP54/UL Type 12##IP54/UL Type 12 frames are designed for use in environments where the drive is exposed to both dust and water. |
| Cross-Plant Configurable Material | iC7-Automation Frequency Converter |
| Mains voltage | 05||380-500 V AC##Voltage range 380-500 V AC - Current rating given at 400V AC |
| Option slot A | +CAX0||None##Option slot is empty, but available to add option later |
| Option slot B | +CBXX||None, not upgradable##Option slot is not available |
| Product group | IC7-60||iC7-60##Product is based on iC7-60 hardware series |
| Product category | FA||Frequency converter,air-cooled |
| Option slot C | +CCX0||None##No option in option slot. Field upgrade possible |
| Option Slot E | +CEX0||None##No option in option slot. Field upgrade possible |
| Integrated common-mode filter | +AIXX||None##No High Frequency common mode filter integrated |
| Current rating | -1120||1120 A |
| Mains input device | +AJFD||AC fuses and mains switch##Input mains switch and AC fuse input protection |
| ECCN EU | Y901||Y901 |
| Functional safety | +BEF2||STO, SS1-t, fieldbus##STO (Safe Torque Off), SS1-t (Safe Stop 1, time controlled), configurable inputs and safe fieldbus support (refer to selection group "Communication interface, X1/X2) - can be upgraded later with more Functional Safety related functionality |
| Language package | +EL01||Global##Global language package - See Technical Documentation for detailed information |
| Frame designation | FB12||FB12 |
| Extra environmental protection | +AGCX||Coated boards##Coated printed circuit board for extra protection |
| EMC category | F3||C3 category##Suitable for installation in the 2nd environment only, max. motor cable length up to 300 meters |
| Heat sink access panel | +APXX||None##No heat sink access plate |
| Humidity protection device | +AHXX||None##None |
| Interface board | +BISR||MicroSD card reader and RTC##Interface board, MicroSD card reader and Real Time Clock (RTC) with battery backup |
| Integrated brake chopper | +ACXX||None##No brake chopper |
| Control panel | +BF20||Control Panel 2.8 OPX20##Control Panel with user interface, status and fieldbus indicators |
| Output frequency | 0-590Hz||0-590Hz |
| Customer-specific label | +EJXX||None##No customer specific information printed on product label |
| Calculated Gross Weight [kg] | 363.550 |
| Ambient temp LO (1/10 min) | 40°C/104°F||40°C/104°F |
| DC terminals | +ALXX||None##No DC terminals |
| Customization file package ID | +EAXXXXXX||No customization##No customer specific settings |
| Vendor | ERR01||Cannot Determine Vendor |
| Communication interface, X1/X2 | +BAPR||PROFINET RT OS7PR##PROFINET RT - Application class 3. MRP, shared device, PROFIenergy, PROFINET diagnostics (ALARM CR) and extended diagnostics. To enable PROFISAFE use the configuration group "Functional Safety". |
| Ambient temp. high overload | 45°C/113°F||45°C/113°F |
| High speed enabled | +DI6X||No##Output frequency limited to 590 Hz |
| Input current HO (1/10 min) | 963/863A||963/863A |
| Typecode Part 2 | -000215286 |
| Cable entry and EMC plate | +AAST||Standard plate |
| Ambient temp. normal overload | 40°C/104°F||40°C/104°F |
| Brand | iC7 |
| Customer specific application | +DBXX||None |
| Calculated Net Weight [kg] | 310.440 |
| Communication interface, X0 | +BBEL||Ethernet port, no protocol##Control card with Ethernet port X0, but no embedded protocol - can be upgraded later |
| Input current LO (1/10 min) | 1078/990A||1078/990A |
| Additional drive features 5 | +DH5X||None |
| Typical motor power PH (150%) | 560KW(400V)/750HP(460V)||560KW(400V)/750HP(460V) |
| Recommended Plant | ERR01||ERR01 |
| Typecode Part 1 | 7FC-AUFA3N05-1120E54F3 |
| Additional drive features 3 | +DF3X||None |
| Maximum Power Loss LO [W] | 13354||13354 |
| Additional drive features 2 | +DE2X||None |
| Typical motor power PH2 (150%) | 500kW(400V)/650HP(460V)||500kW(400V)/650HP(460V) |
| Additional drive features 4 | +DG4X||None |
| Typical motor power PL (110%) | 630kW(400V)/900HP(460V)||630kW(400V)/900HP(460V) |
| Product type | 3N||3~##Three phase supply - rectifier input |
| Short circuit current rating | 100kA||100kA |
| Additional drive features 1 | +DD1X||None |
| Input Voltage | 3x380-500V||3x380-500V |
| Main unit Width | 698 mm / 27.5 in||698 mm / 27.5 in |
| Control Board type | A5E||Advanced Ethernet A5E##Advanced control board with Dual Ethernet interface and 24V external supply |
| Product View (Switch) | GLBL||Global (Standard) |
| Ambient temp HO2 (1/5 min) | 45°C/113°F||45°C/113°F |
| Input current in Normal Overlo | 1078/990A||1078/990A |
| Ambient temp HO (1/10 min) | 45°C/113°F||45°C/113°F |
| Input curent HO2 (1/5 min) | 860/755A||860/755A |
Evet, DES Teknoloji, Danfoss Türkiye partneridir. İncelediğiniz Danfoss iC7-Automation Frequency converter,air-cooled, 3~, 380-500 V AC, 1120 A, 630 kW/900 hp, IP54/UL Type 12, FB12 ürünü %100 orijinal olup fabrika garantisi altındadır.
Evet. DES Teknoloji olarak uzman mühendis kadromuzla Danfoss sürücüleriniz için yetkili bakım, onarım, yedek parça ve test hizmeti sunmaktayız.
Satış sonrası mühendislik hizmetlerimiz kapsamında cihazın pano montajı, parametre ayarları ve sahada devreye alınması konularında teknik destek sağlamaktayız.
Sayfadaki 'Proje İçin Teklif Alın' butonuna tıklayarak veya iletişim numaralarımızdan satış mühendislerimize ulaşarak özel iskontolu fiyat teklifinizi hemen alabilirsiniz.