🔍 Büyüt
| Teknik Parametre | Değer |
|---|---|
| Modelcode01 | IC7-30FA3H04-61A0E21F2 |
| Modelcode02 | +AGCX |
| Modelcode03 | +BAIX+BDBA |
| Modelcode05 | +DAAQ |
| Modelcode04 | +BEG1+BF20+CAC0+CCXX |
| Typecode Part 1 | 7FC-AQFA3H04-61A0E21F2 |
| Typecode Part 2 | -000215299 |
| ECCN EU | Y901||Y901 |
| ECCN US | 3A999.a||3A999.a |
| Recommended Plant | ERR01||ERR01 |
| Calculated Net Weight [kg] | 36.340 |
| Calculated Gross Weight [kg] | 42.910 |
| Vendor | ERR01||Cannot Determine Vendor |
| Efficiency class-Relative loss | IE2 - 1.95%||IE2 - 1.95% |
| Main unit Depth | 327 mm / 12.9 in||327 mm / 12.9 in |
| Enclosure rating | IP21 / TYPE 1||IP21 / TYPE 1 |
| Main unit Height | 770 mm / 30.3 in||770 mm / 30.3 in |
| Input frequency | 50/60Hz||50/60Hz |
| Main unit Width | 239 mm / 9.4 in||239 mm / 9.4 in |
| Short circuit current rating | 100kA||100kA |
| Input Voltage | 3x380-480V||3x380-480V |
| Additional drive features 2 | +DE2X||None |
| Additional drive features 4 | +DG4X||None |
| Additional drive features 5 | +DH5X||None |
| Additional drive features 3 | +DF3X||None |
| Cable entry and EMC plate | +AAST||Standard plate |
| Customer specific application | +DBXX||None |
| Communication interface, X0 | +BBEL||Ethernet port, no protocol##Control card with Ethernet port X0, but no embedded protocol - can beupgraded later |
| Control panel | +BF20||Control Panel 2.8 OPX20##Control Panel with user interface, status and fieldbus indicators |
| Customer-specific label | +EJXX||None##No customer specific information printed on product label |
| DC terminals | +ALXX||None##No DC terminals |
| Customization file package ID | +EAXXXXXX||No customization##No customer specific settings |
| Communication interface, X1/X2 | +BAIX||EtherNet/IP OS7IP + Multilic.##EtherNet/IP - DLR. To enable CIP safety use the configuration group "Functional Safety". With fieldbus multi license. |
| High speed enabled | +DI6X||No##Output frequency limited to 590 Hz |
| Extra environmental protection | +AGCX||Coated boards##Coated printed circuit board for extra protection |
| EMC category | F2||C2 category##Suitable for installations in the 2nd environment, max. motor cablelength up to 150 meters. Use in the 1st environment is possible whenoperated and installed by qualified personnel. The warning informationand installation instructions supplied by the manufacturer must beobserved |
| Heat sink access panel | +APXX||None##No heat sink access plate |
| Humidity protection device | +AHXX||None##None |
| Interface board | +BIXX||None##Connection to control panel |
| Integrated brake chopper | +ACXX||None##No brake chopper |
| Integrated common-mode filter | +AIXX||None##No High Frequency common mode filter integrated |
| Current rating | -61A0||61 A |
| Mains input device | +AJXX||None##No mains device |
| Functional safety | +BEG1||STO int diagn., not upgradable##STO (Safe Torque Off) only, with internal diagnostics - not possible toupgrade later with FS related functionality |
| Language package | +EL01||Global##Global language package - See Technical Documentation for detailedinformation |
| Frame designation | FK07||FK07 |
| Mains voltage | 04||380-480 V AC##Voltage range 380-480 V AC - Current rating given at 400V AC |
| Option slot A | +CAC0||General Purpose I/O OC7C0##Option with 3xDI, 2xDO, 2xAI, 1xAO and support for temperature sensors(Pt100, Pt1000, Ni1000, KTY types) |
| Option slot B | +CBXX||None, not upgradable##Option slot is not available |
| Product group | IC7-30||iC7-30##Product is based on iC7-30 hardware series |
| Product category | FA||Frequency converter,air-cooled |
| Option slot C | +CCXX||None, not upgradable |
| Option Slot E | +CEX0||None##No option in option slot. Field upgrade possible |
| Option slot D | +CDX0||None##No option in option slot. Field upgrade possible |
| Product software ID | +ECXXX||Latest released version##Latest official released version |
| Product series | +DAAQ||iC7-Aqua |
| Standard I/O | +BDBA||4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO##Basic I/O (4 DI, 2 DI/DO, 2 AI, 1 AO, 2 NO/NC relays) |
| Protection rating | E21||IP21/UL Type 1##IP21/UL Type 1 frames are designed for indoor installations. |
| Touch protection | +AMXX||None##No touch protection |
| Product specific marine cert. | +VBXX||None##No approval |
| Technical documentation | +EGIN||Installation guide##Includes Installation Guide and Safety Guide |
| Power rating | 30K||30 kW/40 hp |
| Output frequency | 0-590Hz||0-590Hz |
| Continous current IH (1/10min) | 43/40A||43/40A |
| Continous current IL (1/10min) | 61/55A||61/55A |
| Maximum Power Loss LO [W] | 889||889 |
| Typical motor power PL (110%) | 30kW(400V)/40HP(460V)||30kW(400V)/40HP(460V) |
| Typical motor power PH (150%) | 22KW(400V)/30HP(460V)||22KW(400V)/30HP(460V) |
| Product Catalog | NO_VIEW||NO VIEW |
| Additional drive features 1 | +DD1X||None |
| Product type | 3H||3~, low-harmonic drive##Low Harmonic Drive - three phase supply |
| Control Board type | B5E||Standard Ethernet B5E##Standard control board with Dual Ethernet interface and 24V external supply |
| Product View (Switch) | GLBL||Global (Standard) |
| Ambient temp HO (1/10 min) | 50°C/122°F||50°C/122°F |
| Input current HO (1/10 min) | 37/30A||37/30A |
| Ambient temp LO (1/10 min) | 40°C/104°F||40°C/104°F |
| Input current LO (1/10 min) | 50/41A||50/41A |
Evet, DES Teknoloji, Danfoss Türkiye partneridir. İncelediğiniz Danfoss iC7-Aqua Frequency converter,air-cooled, 3~, low-harmonic drive, 380-480 V AC, 61 A, 30 kW/40 hp, IP21/UL Type 1, FK07 ürünü %100 orijinal olup fabrika garantisi altındadır.
Evet. DES Teknoloji olarak uzman mühendis kadromuzla Danfoss sürücüleriniz için yetkili bakım, onarım, yedek parça ve test hizmeti sunmaktayız.
Satış sonrası mühendislik hizmetlerimiz kapsamında cihazın pano montajı, parametre ayarları ve sahada devreye alınması konularında teknik destek sağlamaktayız.
Sayfadaki 'Proje İçin Teklif Alın' butonuna tıklayarak veya iletişim numaralarımızdan satış mühendislerimize ulaşarak özel iskontolu fiyat teklifinizi hemen alabilirsiniz.